Operation Cub 200/300/300 HD
wcghi_tx000720gb.fm 22
3.10 Starting the Machine
3.10.1 Perform the necessary preliminary checks. See section Preliminary
Checks.
3.10.2 If using the remote thermostat, connect it to the control panel at the
remote thermostat receptacle. Place the remote thermostat in the area
to be heated. Set it to the desired temperature.
Note: If the ambient temperature is below 32°F (0°C), it may be
necessary to preheat the fuel. See section Preheating the Fuel Filter
and Nozzle Heater.
3.10.3 Move the power switch to the On “I” position.
The blower will turn on immediately.
The burner will go through a prepurge cycle and then light.
The burner will continue to fire until the temperature of the space
being heated reaches the temperature set by the thermostat. At
that time, the burner shuts down but the blower will remain on.
If not using the remote thermostat, the blower will continue to
operate until shutdown.