Operation Cub 200/300/300 HD
wcghi_tx000720gb.fm 18
3.5 Machine Location
The Air Heater machines may be located outdoors or in any
environment that requires heating. When locating a machine within the
area to be heated, the exhaust gases must be vented to the outdoors.
The machines must be installed:
By qualified personnel who have read and understood all
supplied instructions.
On a flat, firm surface.
With the following minimum clearances:
3.05 m (10 ft.) to front.
0.61 m (2 ft.) to rear.
0.61 m (2 ft.) to sides.
1.52 m (5 ft.) to top.
0.915 m (3 ft.) to flue pipe.
3.6 Suggested Venting
See Graphic: wcghi_gr003990
Exhaust gas from this machine CAN KILL YOU IN MINUTES. The
exhaust contains carbon monoxide, a deadly poison you can not see
or smell. This machine must be properly vented to reduce the risk of
carbon monoxide poisoning.
When installing vents:
Adhere to all local and national codes.
Consult all appropriate governing bodies or local contractor for
venting and fresh air requirements.
Place the machine in a manner that avoids excessive vent bends
(elbows), and long horizontal runs.
Keep air inlets and outlets free from obstruction.
Route the venting pipes in a manner that avoids any flammable
material.
Route the venting pipes in a manner that avoids contact with
humans.
WARNING